Keterangan :
EMERGENCY EXIT
EMERGENCY LIGHTING FIXTURES EJB08
Type of protection: II 2 GD EEx d ( ia) IIB - T6 T85° C
II 2 ( 2) GD EEx d ( ib) IIB - T6 T85° C
II 2 GD EEx d IIB - T6 T85° C
Conformity: Direttiva 94/ 9/ CE ( ATEX)
Applicable standards: EN 60079.0, EN 60079.1, EN 60079.11,
EN 61241, EN 60529
Certificate of conformity: CESI 03 ATEX 342
Degree of protection: IP 65
Room temperature of use: -20° C + 40° C
Zones of use: 1 - 2 - 21 - 22
EJB 08 lighting fixture has been designed and manufactured so as to
comply with the Italian and European safety requirements in force. Its
purpose is to provide for a reliable emergency light source, indipendent
of the mains and permitting the restart of the service or the avacuation
of the dangerous area, where necessary. The 8 W 205 lumen
tubular fluorescent lamp, contained into the flameproof enclosure, can
be either permanently connected to the main or automatically inserted
via an inverter which changes over the supply to the nickel-cadmium
battery cells in case of voltage black out.
The lighting fixture is provided with two hooks for wall suspension.
Equipped with sign-boards, it can be conveniently used for emergency
or danger warnings.
Electrical characteristics
Rated voltage: 220 V 50 Hz
Ni-Cd storage battery: 3, 6 V 4 A/ h minimum autonomy: 90 min.
Fluorescent lamp: 8 W