KYORITSU 6050 (LOOP+RCD)[22 Mar. 2009, 20:42:11]
Keterangan
� Kew Combitester provides the ultimate in Microprocessor technology offering Loop and RCD tests with a comprehensive memory and downloading test results.
� LOOP Impedance 200/2000© range measurement is carried out using a test current of 15mA. This current will not trip RCD�s rated at 30mA or greater.
� High resolution for low Loop Impedance (resolution of 0.01©) on 20© range.
� Direct reading of Prospective Short Circuit Current (PSC) and earth fault current.
� RCD tests at 0 and 180 degree phase angle switch permit quick tests and consistent readings.
� Test of a large kind of RCD's Standard, Selective, AC and A (DC sensitive breakers).
� Constant current source circuitry ensures that a fluctuating mains voltage does not affect the accuracy of readings.
� RCD Ramp test in order to indicate the actual tripping current of RCD.
� Contact Voltage Reading (UC). with two selectable contact voltage limits
(50 and 25V).
� Visual indication of correct wiring status and automatic lock-out if test resistors overheats.
� Designed to IEC 61010-1, IEC 61557 and high protection degree IP54.
� The stored data can be transferred to PC via Optical Adapter Model 8212-RS232C and 8212-USB.
Loop Impedance Ranges
(Z reading) : 20/200/2000©
Loop Impedance Ranges
without tripping RCDs : 200 and 2000© with 15mA of test current
Max test current on Loop ranges : 3A (20©) / 15mA (200 and 2000©)
PSC / Earth Fault Current Ranges : 200/2000A/20kA
RCD Test AC Type
(Standard and Selective) : � 1/2
� 1
� 5
Auto Ramp 10, 30, 100, 300, 500, 1000mA
10, 30, 100, 300, 500, 1000mA
10, 30, 100mA
10, 30, 100, 300, 500mA
RCD Test A Type
(Standard and Selective) : 10, 30, 100, 300, 500mA
RCD Test Currents multipliers : � 1/2, � 1, � 5
(max 1000mA type AC)
(max 500mA type A)
RCD Test Time Duration : 1000ms: � 1/2, � 1, DC
200ms: � 5, DC (500mA), and � 1 (1000mA)
RCD Ramp Test : From 20% to 110% of I�n (AC type)
Contact Voltage Block (RCD) : 50V and 25V
Contact Voltage Reading (RCD) : 100.0V
Phase and Earth
(2 wires only) measurements : RCD (without DC)
LOOP
Working Voltage for Loop Tests : 20©: 230V+10%-15%
200/2000©: 230V+10%-15% and 400V+10%-15%
Working Voltage for RCD Tests : 230V+10%-15%
Voltage Test : 100 ~ 260V
(LOOP 200/2000©, PSC 200A:100 ~ 440V)
Memory : 300 memory locations
PC Software, Connection Cable : optional with 8212-USB, 8212-RS232C
Safety Standards : IEC 61010-1 CAT.III 300V, IEC 61557
Power Source : 8 � 1.5V R6P(AA)
Dimensions : 186(L) � 167(W) � 89(D)mm
Weight : 980g
Accessories Included : Molded Plug Test Lead 7125-EU
Pouch for Test Leads
Instruction Manual
Shoulder Strap
Batteries
Optional Accessories : 7121 (Distribution Board Test Leads)
8212-RS232C
(RS232C adaptor with KEW Report (Software))
8212-USB
(USB adaptor with KEW Report (Software))