Keterangan
4102A Soft Case Model
4102A-H Hard Case Model
Product Catalogue
� The latest circuit design permits the instrument to operate with the minimum of influence from earth voltage and earth resistance of auxiliary earth spikes.
� Dust and drip proof. (designed to IEC 529 IP54)
� Earth resistance value can be read directly from the scale.
� Designed to meet IEC 61010-1 safety standard.
� Capable of measuring earth voltage.
� Small and lightweight. Shock resistant new case material.
� 2mA measuring current permits earth resistance tests without tripping earth leakage current breakers in the circuit under test.
� Lead wire connection to C and P terminals and proper auxiliary earth resistance can be checked by "OK" lamp. Lead wire connection to C and E terminals is good when "OK" lamp is illuminated.
Measurement
Ranges : Earth Resistance: 0~12 ©/0~120 ©/0~1200 ©
Earth Voltage [50,60Hz]: 0~30V AC
Accuracy : Earth Resistance: ±3% of full scale
Earth Voltage: ±3% of full scale
Overload Protection : Earth Resistance: 276V AC for 10 seconds
across 2 of the 3 terminals
Earth Voltage: 276V AC for 1 minute
Safety Standard : IEC 61010-1 CAT.III 300V Pollution Degree 2, IEC 61557
Applicable Standards : IEC 60529 IP54
Withstand Voltage : 3700V AC for 1 minute
Power Source : R6P (AA) (1.5V) � 6
Dimensions : 105(L) � 158(W) � 70(D)mm
Weight : 600g approx.
Accessories : 7095 (Test Leads) � 1set (red-20m, yellow-10m, green-5m)
8032 (Auxiliary earth spikes) � 1set
7127 (Simplified measurement probe) � 1set
R6P (AA) � 6
Neck strap
Instruction Manual
Carrying Case : 4102A (Soft Case)
: 4102A-H (Hard Case)
Optional : 7100 (Precision measurement Cord Set)