HIOKI 9694 CLAMP ON SENSOR[10 Mar. 2009, 19:42:38]
Keterangan
Clamp-on Sensors for the POWER QUALITY ANALYZER 3196 and CLAMP ON POWER HiTESTER 3169 :
For input of 5A CT, select our Model 9694, This sensor is are designed with a safety barrier to protect the user from being in direct contact with live conductors and completely meet all CE marking requirements.
Basic specifications :
Rated input current : 5 A AC
Rated output current : 50 mV AC
Accuracy (at 45 to 66 Hz) : Amplitude: ±0.3 % rdg. ±0.02 % f.s. , Full scale (f.s.) is the 3196 range value,
Phase: ±2° or less
Frequency characteristics : 66 Hz to 5 kHz (±1 % or less from accuracy)
Max. allowable input : continuous 50 A rms (45 to 66 Hz)
Max. circuit voltage : 300 V AC rms (insulated wire)
Core jaw dia. : Ø15 mm(0.59 in)
Dimensions, mass : 46 mm(1.81 in)W × 135 mm(5.31 in)H × 21 mm(0.83 in)D, 230 g (8.1 oz), cord length: 3 m(9.84 ft)