Selamat Datang di Indotrade.com
Masuk | Daftar
Anggota Prioritas Prioritas IndotradeTahun ke-16
CV. ANDALAN PRIMA SEJAHTERA ( andalan_ prima@ yahoo.com)
http://indotrade.com/andalanprimasejahter/
`CV. ANDALAN PRIMA SEJAHTERA, Telpon: + 62-21-29253184, 021-29253187, 46560833, 46560834, Fak: 021-29253186 Email : support@andalanprimasejahtera.com
Informasi Kontak
Nama:

Tn. Enangkholis / Heru [Direktur/CEO/Manajer Umum]

E-mail:
Pesan Instan:

ICQ: andalanprimasejahtera
Google Talk:  www.andalaninstrument.com  www.andalaninstrument.com
Y!: edy_girsangta@yahoo.com 
Nomor Telpon:

Nomor telpon Tn. Enangkholis  / Heru di bekasi utara - Indonesia

Nomor Ponsel:

Nomor ponsel Tn. Enangkholis  / Heru di bekasi utara - Indonesia

Nomor Faks:

Nomor faks Tn. Enangkholis  / Heru di bekasi utara - Indonesia

Alamat:

Jl. Muhtar Tabrani Perum Bintang Metropol Blok A-7/16
bekasi utara - Indonesia 17122
Indonesia

Alamat Tervalidasi

http: / / www.andalaninstrument.com
Rata-rata Tinjauan Pemakai

Tidak ada ulasan untuk perusahaan ini

Menulis tinjauan

Jual

KYORITSU Portable Appliance Testers 6202[16 Apr. 2011, 3:20:56]
HargaCALL PRICE
Jumlah Pesanan:
Cara PembayaranTransfer Bank (T/T)
Negara AsalJepang
KYORITSU Portable Appliance Testers 6202

The Model 6202 is a hand-held portable appliance tester, performing four functions to ensure the Safety of ClassI, ClassII and ClassIII 230V appliances. And also can measure the mains voltage.
Readings are displayed on a large liquid crystal display ( LCD) below which are eight LEDs which unambiguously display a pass or fail indication for threshold values dictated by DIN VDE 0701/ 0702

This instrument is suitable for performing tests as required by the following standards.
DIN VDE 0701-1 ( 240) : 2000 Repairing, modification and testing of electrical equipment
DIN VDE 0702 : 2004
Periodic inspection for electrical equipment

Spesifikasi :
* RPE 20© + / 20© - Protective Conductor Test
- Measuring Range : 0~ 19.99©
- Resolution of Measurement : 10m©
- Short Circuit Current : 200~ 250mA
DC
- Open Circuit Voltage : ± 5.0± 0.4V DC
- Accuracy : ± ( 2% rdg+ 3dgt)

* RINS 200M© Insulation Resistance
- Measuring Range : 0~ 19.99/ 199.9M© ( 2ranges auto)
- Resolution of Measurement : 10k© /
100k©
- Rated Voltage : > 500V DC ( + 50% / -0% )
- Rated Current : > 1mA
- Short Circuit Current : 14mA ( max.)
- Accuracy : ± ( 2% rdg+ 3dgt)

* IEL 20mA Equivalent Leakage Current
- Measuring Range : 0~ 19.99mA
- Resolution of Measurement : 0.01mA
- Measuring Voltage : 30V AC
- Internal Resistance ( RA Meter) : 2k©
- Accuracy : ± ( 2% rdg+ 3dgt)

* IL 2mA Contact Current
- Measuring Range : 0~ 1.999mA
- Resolution of Measurement : 0.001mA
- Internal Resistance ( RA Meter) : 2k©
- Accuracy : ± ( 2% rdg+ 3dgt)

* VOLT AC Voltmeter
- Measuring Range : 180~ 260V
( 50/ 60Hz)
- Resolution of Measurement : 1V
- Accuracy : ± ( 2% rdg+ 3dgt)

* I LINE Current Consumption
- Measuring Range : 0~ 16A AC
- Resolution of Measurement : 0.01A
- Accuracy : ± ( 2% rdg+ 3dgt)

* General
- Supply Voltage : 230V± 10%
- Frequency : 50/ 60Hz± 1%
- Dimension : 185 ( L) × 167 ( W) × 89 ( D) mm
- Weight : 1kg

* Applicable Standards
- IEC 61010-1 : CAT.III 300V, Pollution Degree2
- IEC 60950 : Safety of Information Technology Equipment
- IEC 61326-1 : EMC requirements
- Accessories : 7125 ( Power Cord ( EU) ) , 7129 ( Test Leads with Alligator Clip) , 7161 ( Flat Test Bar) , Probe Case, Shoulder Strap, Instruction Manual
- Optional : 7121A ( Test lead)
Anda mendapat [3] permintaan baru. Ke Menu Anggota
Depan - Penawaran Dagang - Daftar Produk - Daftar Permintaan - Daftar Kerjasama - Daftar Perusahaan
© 2025 Indotrade.com. Hak Cipta Dilindungi Undang-undang.